2 Volt AGM Deep Cycle Solar Batteries
Electrical Properties
Dimensions
Nominal Capacity Ampere Hours @ 25° (77° F) to 1.75 volts per cell.
1
Hour
Rate
2
Hour
Rate
4
Hour
Rate
8
Hour
Rate
24
Hour
Rate
48
Hour
Rate
72
Hour
Rate
100
Hour
Rate
120
Hour
Rate
Part Number
Voltage
Industry Reference
PVX-5040T
2
2
24
312
396
408
444
504
540
561
574
582
PVX-5340T
2
31
330
420
432
474
534
570
591
604
612
PVX-6240T
1
2
27
390
492
510
558
624
672
696
710
720
PVX-6480T
2
31
408
516
528
582
648
708
732
746
756
PVX-6720T
2
GC2
429
540
555
612
672
738
768
780
789
PVX-7680T
1
2
31
474
600
618
678
768
834
864
876
894
PVX-9150T
2
GC2 Tall
570
735
810
840
915
1005
1044
1062
1074
PVX-12150HT
2
L16
798
1035
1080
1128
1215
1272
1302
1329
1344
1: minimum order of 84 solar batteries applies.
2: minimum order of 96 solar batteries applies.
Sun Xtender® Battery Specifications
Adobe Acrobat Reader is required to view PDF files. This is a free program available from the
Adobe Website
. Follow the download instructions on the Adobe Website to get a copy Adobe Acrobat Reader.
Web Accessibility Statement
Sun Xtender® Solar Batteries
P: 1-800-757-0303 | F: 626-813-1235
2009 West San Bernardino Road, West Covina, CA 91790
© 2017 Concorde® Battery Corporation